For telecom sites the standby diesel generator set you need runs from 6 to 240 kW; Eastern Lion builds these sets around the Cummins, Yuchai, Kofo engines in 50 and 60 Hz, in open frame, silent canopy, trailer, ATS and parallel configurations, and every set is tested at full load before shipment.
How to size the set
Standby duty: the set has to carry the whole connected load plus the starting current, so we size it above the running load. The table below lists the standby ratings of the real models for every typical load of this application.
| Typical load | Standby power to look at | Models that cover it |
|---|---|---|
| 5 kW | 8 – 11 kW | GFS-P10
Engine By Perkins Series · 8 kW GF/GFS-KF10 Engine By Kofo Series · 11 kW GFS-P14 Engine By Perkins Series · 11 kW |
| 10 kW | 13 – 13 kW | GF/GFS-KF12
Engine By Kofo Series · 13 kW GF/GFS-YC12 Engine By Yuchai Series · 13 kW GF/GFS-YN12 Engine By Yunnei Series · 13 kW |
| 20 kW | 24 – 24 kW | GFS-C22
Engine By Cummins · 24 kW GFS-C22I Engine By Cummins · 24 kW GF/GFS-HC31 Engine By Huachai Series · 24 kW |
| 50 kW | 64 – 64 kW | GFS-C58
Engine By Cummins · 64 kW GF/GFS-HC81 Engine By Huachai Series · 64 kW GF/GFS-KF58 Engine By Kofo Series · 64 kW |
| 100 kW | 120 – 122 kW | GF/GFS-LW108
Engine By Lovol Series · 120 kW GFS-P150 Engine By Perkins Series · 120 kW GFS-W153 Engine By Longxin Series · 122 kW |
| 200 kW | 244 – 244 kW | GFS-C220
Engine By Cummins · 244 kW GF/GFS-KF220 Engine By Kofo Series · 244 kW GFS-306K Engined By Kaixun Series · 244 kW |
The ratings follow ISO 8528. The final model depends on the voltage, the fuel autonomy, the enclosure and the ambient temperature - send us the load and we will confirm it in writing.
What this application needs
The load of a telecom site
A telecom site is small but the equipment is sensitive: the base station, the microwave link, the rectifier and the battery bank. The generator normally feeds the rectifier on the -48 V DC bus, and the site controller decides when the set starts, how long it runs and when it stops. Sizing is straightforward: the total AC load of the site, plus the starting current of the biggest motor, plus a margin for the rectifier’s own losses.
The fuel decides the autonomy
On a telecom site the fuel is the real constraint, because the refuelling truck has to reach the site. A 100 kW set burns about 26 litres an hour at full load, so a 500 litre day tank is roughly nineteen hours of running. The usual arrangement is a large bulk tank on site, a transfer pump and a smaller day tank next to the set, with a level sensor on both. We size the tanks from the consumption and the refuelling interval you give us, and we quote the pipework with it.
Security is part of the specification
The equipment on a telecom site is worth stealing, and the fuel is worth draining. The enclosure is lockable, the filler cap and the control panel are lockable, and the doors use anti-tamper screws. On sites that have had problems, the GSM monitoring with a door sensor and a fuel level sensor is worth more than the lock on its own, because it tells you when something happens rather than after it happens.
The noise in a residential area
A tower next to houses is a common situation. The silent canopy set with acoustic lining and a discharge silencer brings the noise down to roughly 70 dB(A) at 7 m, and the exhaust is ducted up and away from the doors and windows of the nearest building. In a country with strict night-time noise limits we quote the canopy with the extra roof insulation and the low-temperature radiator pack.
Heat, dust and altitude
A site in the desert or in the mountains takes power away from the set. The standard rating is for 40 °C at sea level; above that, or above 2000 m, the output has to be derated or the set specified for the derated rating. Send the altitude and the highest ambient temperature and we will confirm the rating in writing, together with the fuel consumption at the site altitude, which is higher than the catalogue figure.
Remote monitoring
The start, the stop, the fuel level, the temperature and the fault codes can be reported over GSM or Wi-Fi to the network operations centre. That is what lets a small team look after hundreds of sites: the site controller tells them what happened, and the fuel order can be placed before a site goes down.
What we deliver
Open frame or silent canopy, 50 Hz or 60 Hz, with the day tank, the bulk tank, the transfer pump, the heaters, the battery charger, the float charger and the monitoring written into the same quotation. Every set is run at full load in the factory before it is loaded, and the test record travels with the machine.
The series used for this job
Engine By Cummins
22 – 444 kW · 50 Hz · 24 models
View detailsEngine By Yuchai Series
12 – 1378 kW · 50 Hz · 21 models
View detailsEngine By Kofo Series
10 – 338 kW · 50 Hz · 19 models
View detailsEngine By Yuxing Series
22 – 338 kW · 50 Hz · 19 models
View detailsEngine By Perkins Series
7.2 – 2000 kW · 50 Hz · 17 models
View detailsEngine By Huachai Series
13 – 289 kW · 50 Hz · 16 models
View detailsQuestions buyers ask about this application
Tell us the load and the site
Send the running load, the voltage and where the set has to run. Our engineers answer with the model, the layout and the price within one working day.