For mining sites the standby diesel generator set you need runs from 120 to 1920 kW; Eastern Lion builds these sets around the Cummins, Perkins, Yuchai engines in 50 and 60 Hz, in open frame, silent canopy, trailer, ATS and parallel configurations, and every set is tested at full load before shipment.
How to size the set
Standby duty: the set has to carry the whole connected load plus the starting current, so we size it above the running load. The table below lists the standby ratings of the real models for every typical load of this application.
| Typical load | Standby power to look at | Models that cover it |
|---|---|---|
| 100 kW | 120 – 122 kW | GF/GFS-LW108
Engine By Lovol Series · 120 kW GFS-P150 Engine By Perkins Series · 120 kW GFS-W153 Engine By Longxin Series · 122 kW |
| 200 kW | 244 – 244 kW | GFS-C220
Engine By Cummins · 244 kW GF/GFS-KF220 Engine By Kofo Series · 244 kW GFS-306K Engined By Kaixun Series · 244 kW |
| 500 kW | 600 – 611 kW | GFS-750K
Engined By Kaixun Series · 600 kW GF/GFS-C540 60 HZ Engine By Cummins Series 2 · 600 kW GF/GFS-YC550 Engine By Yuchai Series · 611 kW |
| 1000 kW | 1200 – 1222 kW | GFS-P1500
Engine By Perkins Series · 1200 kW GF/GFS-C1100 Engine By Cummins 2 · 1222 kW GF/GFS-C1100 60 HZ Engine By Cummins Series 2 · 1222 kW |
| 1600 kW | 2000 – 2000 kW | GFS-P2500 Engine By Perkins Series · 2000 kW |
The ratings follow ISO 8528. The final model depends on the voltage, the fuel autonomy, the enclosure and the ambient temperature - send us the load and we will confirm it in writing.
What this application needs
The mine runs on prime power
A mine or a quarry is not a standby site. The sets normally run every day and often around the clock, and there is no grid behind them. That changes the specification: the fuel system, the cooling and the service plan are designed for thousands of hours a year instead of for a few test runs a month, and the set is bought with the spare parts for that horizon in mind.
The load
The crusher, the conveyor, the ventilation fans, the pumps, the compressors, the workshops and the camp are all fed from the site power system. The load is not steady: the crusher draws a heavy peak when it starts, and the fans run with a high starting current. The set is therefore sized on the connected load with the starting current of the largest motor added, and the distribution is usually split so that the large motors are started in a controlled sequence.
The fuel is the real constraint
On a remote site the fuel is a long way away and the weather can close the road. The autonomy is quoted from the fuel tank level, as ISO 8528 requires, and 8 to 24 hours at full load is the normal minimum; remote sites plan further. A bulk tank of 5000 to 20000 litres next to the set, a transfer pump, a bund and a level alarm are the usual arrangement, with the daily tank holding enough to run a shift.
Dust, altitude and heat
Dust clogs the air filter and wears the bearings, so we fit a larger air cleaner with a cyclone pre-cleaner and shorten the filter service interval well below the manual. At altitude the air is thinner: at 3000 m a typical set has to be derated by about 25 to 30 percent, and that has to be designed into the model rather than discovered on site. The same applies to the desert sites, where the ambient temperature of 50 °C takes power off the rating. Send the altitude and the highest temperature and we confirm the rating in writing.
The enclosure and the installation
The set on a mine site is either an open frame with a canopy over it, a silent canopy set, or a containerised set with a lifting frame so it can be moved with a crane. The enclosure has to survive the dust, the rain and the sun, so the paint system and the anti-corrosion coating are chosen for the site: a coastal mine wants a heavier coating than an inland one.
Protection and safety
The electrical protection is matched to the site: the circuit breakers, the earth fault arrangement and the neutral treatment are decided with the client’s own electrical engineer, and we supply the set with the protection written into the quotation. Where the fuel and the electrical equipment share a room, the ventilation and the fire separation are part of the layout.
What we deliver
Prime or standby rated sets, 50 Hz or 60 Hz, open frame, silent canopy or containerised, with the fuel system, the air filtration, the heaters, the battery charger and the monitoring written into the same quotation. Every set is run at full load in the factory before it is loaded, and the test record travels with the machine.
The series used for this job
Engine By Cummins 2
200 – 1311 kW · 50 Hz · 26 models
View detailsEngine By Perkins Series
7.2 – 2000 kW · 50 Hz · 25 models
View detailsEngine By Yuchai Series
12 – 1378 kW · 50 Hz · 24 models
View detailsEngine By Wuxi Series
48 – 1111 kW · 50 Hz · 22 models
View detailsEngine By Cummins
22 – 444 kW · 50 Hz · 19 models
View details60 HZ Engine By Cummins Series 2
200 – 1222 kW · 60 Hz · 18 models
View detailsQuestions buyers ask about this application
Tell us the load and the site
Send the running load, the voltage and where the set has to run. Our engineers answer with the model, the layout and the price within one working day.